English • 繁體简体Mobile

Products mainpage » IT&Infrastructure Networking Solutions » Data Center Energy » Huawei » UPS » UPS5000-A

AC power is rated at 380V/400V/415V AC for medium and large data centers, scheduling centers, control centers, and management centers.

Specifications:

Item

30 kVA/40 kVA

60 kVA/80 kVA/120 kVA

200 kVA/300 kVA

400 kVA/500 kVA

600 kVA

800kVA

Rated Capacity

30 kVA/30 kW

40 kVA/40 kW

60 kVA/60 kW

80 kVA/80 kW

120 kVA/80 kW

200 kVA/200 kW

300 kVA/300 kW

400 kVA/380 kW

500 kVA/475 kW

600 kVA/570 kW

800 kVA/760 kW

Input and Output Systems

Three-phase, five-wire

Rated Voltage

380V/400V/415V AC

Battery Voltage

360V to 380V DC (Number of batteries: 30 to 40, 32 by default)

Overload Capacity

Inverter: 110% load for 60 min; 125% load for 10 min; 150% load for 1 min

Output Power Factor

1

0.95

Efficiency

95.7%

96%

Noise

≤ 58 dB

≤ 64 dB

≤ 68 dB

≤ 70 dB

Dimensions (H x W x D)

500 mm x 264 mm x 800 mm

1,020 mm x 440 mm x 850 mm

2,000 mm x 600 mm x 850 mm

2,000 mm x 1,200 mm x 850 mm

2,000 mm x 2,000 mm x 850 mm

2,000 mm x 2,400 mm x 850 mm

Communication

Dry contacts, RS485, and SNMP

 

Privacy Policy Terms of Use Feedback